LCD Message Codes

Message
BAD EE
System Error. A system error typically represents a failure of the EE PROM. Contact the factory for
replacement.
EC XX
The XX refers to the Modbus register 8 message code shown in
Register
message codes in hex.
DX80 display shows *ERROR: The Gateway uses fully-acknowledged polling to ensure each Node
radio link is robust. If a prescribed number of sequential polling cycles are not acknowledged by a
Node, the Gateway considers the radio link with that Node to be timed out. All outputs on the Node in
question are set to the user-selected default state or the output holds its last state, depending on
user configuration options set using the User Configuration Tool. If the Node's radio link recovers
and the Gateway or Gateway Pro determines enough acknowledged polling messages have
accumulated, the link is reinstated.
EC 53
Radio Device (polling/heartbeat) Timeout. (Decimal value 13569.) A Node dropped out of the
wireless network based on the parameters defined for polling or heartbeat. For more information,
see Message Code 35 in
EC 54
Modbus time-out. A Gateway timeout (time of inactivity on the serial channel) was detected. For more
information, see Message Code 36 in
No LCD
All DX80s display "POWER" on the LCD for the first 5 to 10 seconds after applying power. A
Gateway's LED 1 is solid green when power is connected. Nodes flash a red LED 2 every 3 seconds
or a green LED 1 every second depending on the radio link status.
Battery-powered devices turn off the LCD after 15 minutes (factory default). Push any button to
reactivate the LCD. Battery-powered devices may be in storage mode. To put battery powered
devices into storage mode, hold button 1 for 5 seconds. To return from storage mode, hold button
1 for 5 seconds.
Recheck the power connections and power requirements. Battery-powered devices require 3.6 to
5.5 VDC. Non-battery powered devices require 10 to 30 VDC.
After replacing the battery, allow up to sixty seconds for the device to power up.
3A6715B
8. The LCD displays the message code in decimal; host-controlled systems read the
Modbus Message Codes for Register
Solution
Modbus Message Codes for Register
Troubleshooting
Modbus Message Codes for
8.
8.
23