Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 99

Inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E11
Remote control:
1. Applicable model
Models FDC100
2. Error detection method
Indoor unit address has been set
using the "Master IU address
set" function of remote control.
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake of address setting
method
(
Address setting from remote
control can't be done.
Note:
RUN light TIMER light
Indoor
display
Green LED Red LED
Outdoor unit
control PCB
Keeps flashing stays OFF
5. Troubleshooting
E11 occurs
Is "Master IU
address set" function of remote
control used?
In case the wiring is below and "Master IU address set"
is used, E11 is appeared.
Interface kit
)
Address setting error of
Content
(Models FDC100 only)
Diagnosis
YES
・ ・ ・ ・ ・ ・
IU
IU
IU
・ ・ ・ ・ ・ ・
・ ・ ・ ・ ・ ・
R/C
98
-
-
'22 • PAC-SM-422
indoor units
Countermeasure
Change of address setting
method
Set the address by DIP
switch SW2 on indoor
unit control PCB.