Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 58

Inverter packaged air-conditioners
Table of Contents

Advertisement

(5) Check of anomalous operation data with the remote control
(a) In case of RC-EX3A remote control
[Operating procedure]
➀ On the TOP screen, touch the buttons in the order of "Menu" ➝ "Service setting" ➝ "Service & Maintenance" ➝
"Service password" ➝ "Set" ➝ "Error display" ➝ "Error history".
➁ When only one indoor unit is connected to the remote control, followings will be displayed.
1. When there is any anomaly: "Loading. Wait a while" is displayed, followed by the operation data at the occurrence
of anomaly
Contents of display
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, and this mode is terminated.
➂ When two or more indoor units are connected to the remote control, followings will be displayed.
1. When there is any anomaly: If the unit having anomaly is selected on the "Select IU" screen, "Loading. Wait a while"
is displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・ Indoor unit No.
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, ant this mode is terminated.
Note When the number of connected units cannot be shown in a page, select "Next".
➃ If you press [RUN/STOP] button, the display returns to the TOP screen.
◎ If you touch "Back" button on the way of setting, the display returns to the last precious screen.
Note When two remote controls are used to control indoor units, the check of anomaly operation data can be made on the master remote control only. (It
cannot be operated from the slave remote control.)
■ Anomaly operation data (Corresponding data may not be provided depending on models. Such items will not be displayed.)
Number
01
02
03
04
05
06
07
08
09
10
11
12
13
21
22
23
24
25
Number 33 details of compressor protection status
26
Models FDC100VNX-W, 100VSX-W
27
Contents of display
28
Normal
29
Discharge pipe temperature protection control
30
Discharge pipe temperature anomaly
31
Current safe control of inverter primary current
32
High pressure protection control
33
High pressure anomaly
34
Low pressure protection control
35
Low pressure anomaly
36
Anti-frost prevention control
37
Current cut
38
39
Data Item
(Operation Mode)
(Set Temperature)
(Return Air Temperature)
(Remote Control Temperature Sensor)
(Indoor Heat Exchanger Temperature Sensor / U Bend)
(Indoor Heat Exchanger Temperature Sensor /Capillary)
(Indoor Heat Exchanger Temperature Sensor /Gas Header)
(Indoor Unit Fan Speed)
(Frequency Requirements)
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit)
(Supply Air Temperature)
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Temperature Sensor)
(Outdoor Heat Exchanger Temperature Sensor)
(Compressor Frequency)
(High Pressure)
(Low Pressure)
(Discharge Pipe Temperature)
Reference page
(Comp Bottom Temperature)
(Current)
P.22
.(a).(i)
(Target Super Heat)
P.22
.(a).(ii)
(Super Heat)
P.24
.(f)
(Discharge Pipe Super Heat)
P.22
.(b).(i) P.23
.(c).(i)
(Protection State No. of The Compressor)
P.22
.(b).(ii) P.23
.(c).(ii)
(Outdoor Unit Fan Speed)
P.23
.(e).(i)
(63H1 On/Off)
P.23
.(e).(ii)
(Defrost Control On/Off)
P.24
.(j)
(Total Running Hours of The Compressor)
P.24
.(f)
(Pulse of The Outdoor Unit Expansion Valve EEVC)
P.24
.(g)
(Pulse of The Outdoor Unit Expansion Valve EEVH)
P.24
.(h)
P.25
.(k)
P.24
.(f)
P.25
.(o)
Number 33 details of compressor protection status
Models FDC100VNX-W, 100VSX-W
No.
Contents of display
"0"
Normal
"1"
Discharge pipe temperature protection control
"2"
Discharge pipe temperature anomaly
"3"
Current safe control of inverter primary current
"4"
High pressure protection control
"5"
High pressure anomaly
"6"
Low pressure protection control
"7"
Low pressure anomaly
"8"
Anti-frost prevention control
"9"
Current cut
"10" Power transistor protection control
"11" Power transistor anomaly (Overheat)
"13" Spare
"14" Dewing prevention control
"15" Current safe control of inverter secondary current
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
"18" Active filter anomaly
Notes(1) Operation data display on the remote control.
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
(2) Common item.
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
57
-
-
'22 • PAC-SM-422
Reference page
P.22
.(a).(i)
P.22
.(a).(ii)
P.24
.(f)
P.22
.(b).(i) P.23
.(c).(i)
P.22
.(b).(ii) P.23
.(c).(ii)
P.23
.(e).(i)
P.23
.(e).(ii)
P.24
.(j)
P.24
.(f)
P.24
.(g)
P.24
.(h)
P.25
.(k)
P.24
.(f)
P.25
.(o)
Notes(1) Operation data displ
Data is dispalyed un
In case of multiple p
(2) Common item.
In heating mode.
During protection co
frequency from indo
In cooling and dehu
During protection co
frequency from indo