Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 134

Inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Indoor display
Remote control:
E54
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
Models FDC100VN(S)X-W,
100VN(S)A-W, 200VSA-W
2. Error detection method
When anomalous voltage
(pressure) is detected
3. Condition of error displayed
If the pressure sensor detects
DC0V or lower and DC4.0V or
higher for 5 seconds continuously
within 2 minutes to 2 minutes
20 seconds after compressor
ON, the compressor stops. When
the compressor is restarted
automatically after 3-minute
delay, but if this anomaly occurs
3 times within 40 minutes.
4. Presumable cause
• Defective low pressure sensor
connection
• Defective low pressure sensor
• Defective outdoor unit control
PCB
• Improper amount of
refrigerant
• Anomalous refrigeration
circuit
Note:
RUN light
Green LED
Keeps flashing
control PCB
Yellow LED
Keeps flashing
5. Troubleshooting
connection of low pressure
sensor connectors (at sensor side
measurement) matched with the value
indicated on the remote
Replace the low pressure sensor.
TIMER light
Content
Red LED
(Models FDC100VN(S)X-W, 100VN(S)A-W,
1-time flash
Diagnosis
Are the
and PCB side) OK?
YES
Are the
pressure (actual
control?
NO
Is
normal condition
restored?
133
-
-
'22 • PAC-SM-422
Low pressure sensor anomaly
200VSA-W only)
Countermeasure
Correct low pressure sensor
NO
connector connection.
Is refrigerant amount
YES
charged properly?
Is there any anomaly on the
refrigeration circuit?
Defective outdoor unit
NO
control PCB➞Replace.
(Defective low pressure
sensor input circuit)
OK
YES