Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 116

Inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Indoor display
Remote control:
E42
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
Models FDC100
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
• After 3-minute delay, the
compressor restarts, but if this
amonaly occurs 4 times within
30 minutes after the intial
detection. (FDC100VN(S)
X-W, FDC100VN(S)A-W only)
4. Presumable cause
• Defective inverter or control
PCB
• Faulty power source
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
RUN light
ON
Green LED
Keeps flashing
control PCB
Yellow LED
1-time flash
5. Troubleshooting
From previous page
Is the
checked result of power
transistor module
OK?
YES
• Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short-circuit of air on indoor and/or outdoor unit?
• At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
sensor normal?
• Is there any anoumalous sound on the compressor?
YES
After
resetting power for
several times does it
become normal?
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
TIMER light
Content
1-time flash
Red LED
1-time flash
(Models FDC100 only)
Diagnosis
NO
NO
 
115
-
-
'22 • PAC-SM-422
Current cut (2/2)
Countermeasure
Defective inverter or
control PCB➞Replace.
Defective inverter or
control PCB➞Replace.