Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 92

Inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Remote control:
WAIT
1. Applicable model
Model FDC100VNP-W
When the remote control
display is extinguished after the
power on.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Blown fuse
• Connection between PCB's
• Blown fuse
• Faulty indoor unit control
PCB
• Defective remote control
• Wire breakage on remote
control
• Faulty outdoor unit PCB
Note:
RUN light
TIMER light
Indoor
display
5. Troubleshooting
Diagnosis
Remote control display is
extinguished after the power on.
Is the
green LED on the indoor unit
flashing?
YES
between wires at the remote control
Are wires
connected properly between the indoor and
the outdoor units?
YES
Is approx.
DC20V detected between 2/N -
Ž on the outdoor unit terminal
block?
YES
Is approx
DC20V detected between -Ž
on the indoor unit terminal
block?
91
-
Communication error at
Content
initial operation (3/3)
(Model FDC100VNP-W only)
NO
Is the
fuse on the indoor unit control
PCB OK?
YES
Is
approx. DC10-11V detected
side after disconnecting the
remote control?
YES
NO
NO
NO
YES
-
'22 • PAC-SM-422
Countermeasure
NO
Replace fuse.
NO
Short-circuit on remote
control wire
Defective remote control
Correct wires.
Defective outdoor unit
PCB➞Replace.
Defective connection wire
(Broken wire)
Noise
Defective indoor unit
control PCB➞Replace.