(3) Auto swing control
Note Even if [ Auto Swing ] is selected, the louver position with anti draft function is fixed to position 1.
(a) RC-EX3A
(i)
Louver control
1)
To operate the swing louver when the air-conditioner is operating, press the "Direction" button on the TOP
screen of remote control. The wind direction select screen will be displayed.
2)
To swing the louver, touch the "Auto swing" button. The lover will move up and down. To fix the swing
louver at a position, touch one of [1] - [4] buttons. The swing lover will stop at the selected position.
3)
Louver operation at the power on with a unit having the louver 4-position control function
The louver swings one time automatically (without operating the remote control) at the power on.
This allows the microcomputer recognizing and inputting the louver motor (LM) position.
(ii) Automatic louver level setting during heating
At the hot start and the heating thermostat OFF, regardless whether the auto swing switch is operated or not (auto
swing or louver stop), the louver takes the level position (in order to prevent blowing of cool wind). The louver
position display LCD continues to show the display which has been shown before entering this control.
(iii) Louver free stop control
If you touch the "Menu" → "Service setting" → "R/C settings" → "Service password" buttons one after
another on the TOP screen of remote control, the "Flap control" screen is displayed. If the free stop is selected
on this screen, the louver motor stops upon receipt of the stop signal from the remote control. If the auto swing
signal is received from the remote control, the auto swing will start from the position before the stop.
(b) RC-E5
(i) Louver control
1)
Press the "LOUVER" button to operate the swing louver when the air-conditioner is operating.
"SWING
2)
To fix the swing louver at a position, press one time the "LOUVER" button while the swing louver is
moving so that four stop positions are displayed one after another per second.
When a desired stop position is displayed, press the "LOUVER" button again. The display stops, changes
to show the "STOP 1
3)
Louver operation at the power on with a unit having the louver 4-position control function
The louver swings one time automatically (without operating the remote control) at the power on.
This allows inputting the louver motor (LM) position, which is necessary for the microcomputer to
recognize the louver position.
Note (1) If you press the "LOUVER" button, the swing motion is displayed on the louver position LCD for 10 second. The display
(ii) Automatic louver level setting during heating
At the hot start with the heating thermostat OFF, regardless whether the auto swing switch is operated or not (auto
swing or louver stop), the louver takes the level position (In order to prevent the cold start). The louver position
display LCD continues to show the display which has been shown before entering this control.
(iii) Louver free stop control
When the louver-free stop has been selected with the indoor function of wired remote control "
the louver motor stops when it receives the stop signal from the remote control. If the auto swing signal is
received from the remote control, the auto swing will start from the position where it was before the stop.
Note When the indoor function of wired remote control "
function "
" is displayed for 3 seconds and then the swing louver moves up and down continuously.
" for 5 seconds and then the swing louver stops.
changes to the "SWING
" display 3 seconds later.
POSITION" in the same way.
POSITION" has been switched, switch also the remote control
11
-
-
'22 • PAC-SM-422
POSITION",