Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 33

Inverter packaged air-conditioners
Table of Contents

Advertisement

(iv) Display sequence of error codes or inspection indicator lamps
■ Occurrence of one kind of error
Displays are shown respectively according to errors.
■ Occurrence of plural kinds of error
Section
Error code on remote
• Displays the error of higher priority (When plural errors are persisting)
control
Red LED on outdoor unit
• Displays the present errors. (When a new error has occurred after the former error was reset.)
control PCB (1)
■ Error detecting timing
Section
Error description
Communication error at
initial operation
Remote control
communication circuit error
Communication error during
operation
Indoor
Excessive number of
connected indoor units by
controlling with one remote
control
Return air temperature sensor
anomaly
Indoor heat exchanger
temperature sensor anomaly
Outdoor air temperature
sensor anomaly
Outdoor heat exchanger
temperature sensor anomaly
Discharge pipe temperature
Outdoor
sensor anomaly
Suction pipe temperature
sensor anomaly
Low pressure sensor anomaly
Compressor under dome
temperature sensor anomaly
Notes (1) This LED isn't installed on models FDC100VNP-W.
(2) Value in ( ) are for the models FDC100VNP-W.
Category of display
Error code
No communication between indoor and outdoor units is
"
"
WAIT
established at initial operation.
Communication between indoor unit and remote control is
interrupted for more than 2 minutes continuously after initial
communication was established.
Communication between indoor and outdoor units is interrupted
for more than 2 minutes continuously after initial communication
was established.
Whenever excessively connected indoor units is detected after
power ON.
-50°C or lower is detected for 5 seconds continuously within 60
No-indication
minutes after initial detection of this anomalous temperature.
-50°C or lower is detected for 5 seconds continuously within 60
No-indication
minutes after initial detection of this anomalous temperature.
Or 70°C or higher is detected for 5 seconds continuously
-45(-55)°C or lower is detected for 5 seconds continuously 3
times within 40 minutes after initial detection of this anomalous
temperature.
Or -45(-55)°C or lower is detected for 5 seconds continuously
within 20 seconds after compressor ON.
-50(-55)°C or lower is detected for 5 seconds continuously 3
times within 40 minutes after initial detection of this anomalous
temperature.
Or -50(-55)°C or lower is detected for 5 seconds continuously
within 20 seconds after compressor ON.
-10(-25)°C or lower is detected for 5 seconds continuously 3
times within 40 minutes after initial detection of this anomalous
temperature.
-50°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
0V or lower or 4.0V or higher is detected for 5 seconds
continuously 3 times within 40 minutes after initial detection of
this anomalous pressure.
-50°C or lower is detected for 5 seconds continuously 3 times
within 40 minutes after initial detection of this anomalous
temperature.
32
-
-
'22 • PAC-SM-422
Error detecting timing