Error code
Indoor display
Remote control:
E35
Outdoor unit
Outdoor unit
inverter PCB
1. Applicable model
Models FDC100VN(S)X-W,
100VN(S)A-W, 200VSA-W
2. Error detection method
For the error detection method,
refer to cooling high pressure
protective control in the
protective control by controlling
compressor rotation speed of
microcomputer control function
for corresponding models.
3. Condition of error displayed
When outdoor heat exchanger
temperature anomaly is detected
5 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop
4. Presumable cause
• Defective outdoor heat
exchanger temperature sensor
• Defective outdoor unit control
PCB
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
• Excessive refrigerant amount
Note:
RUN light
ON
Green LED
Keeps flashing
control PCB
Yellow LED
Keeps flashing
5. Troubleshooting
* For the contents of control, refer to cooling high pressure protective control
in the protective control by controlling compressor rotation speed of micro-
computer control function for corresponding models.
TIMER light
Content
Keeps flashing
Red LED
(Models FDC100VN(S)X-W,100VN(S)A-W,
1-time flash
Diagnosis
* For the characteristics of outdoor
heat exchanger temperature
Are the
sensor, refer to E37.
characteristics of
outdoor heat exchanger
temperature sensor
normal?
YES
Is the
unit operating in the
state of cooling
overload?
NO
Is the high
pressure control
normal?
YES
Is
the temperature
(measured actually) at
detection of error
correct?
102
-
-
'22 • PAC-SM-422
Cooling overload operation
200VSA-W only)
Countermeasure
NO
Replace outdoor heat
exchanger temperature
sensor.
YES
Check unit side.
• Isn't the air circulation
of outdoor unit short-
circuited?
• Are installation spaces
adequate?
• Isn't there any fouling
or clogging on heat
exchanger?
NO
Control operation check *
NO
Defective outdoor unit
control PCB➞Replace.
YES
Excessive refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.