Mitsubishi Heavy Industries SRK100VNXWZRF Service Manual page 144

Inverter packaged air-conditioners
Table of Contents

Advertisement

Indoor display
Error code
Outdoor unit
Remote control:
E59
control PCB
Outdoor unit
inverter PCB
1. Applicable model
Model FDC200VSA-W
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
3. Condition of error displayed
If the compressor fails to startup
for 20 times (10 patterns ×2
times) continuously
4. Presumable cause
• Outdoor fan motor anomaly
• Outdoor unit control PCB
anomaly
• Inverter PCB anomaly
• Anomalous power source
voltage
• Insufficient or excessive
refrigerant amount
• Faulty component for
refrigerant circuit
• Compressor anomaly
(Motor or bearing)
Note: Insulation resistance
• The unit is left for long period without power source or soon after installation, insulation resistance may decrease to several MΩ or lower due to the liquid refrigerant
migrated in the refrigerant oil in compressor. If the electric leakage breaker is activated due to low insulation resistance, check followings.
➀ Check whether the insulation resistance can recover or not, after 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated.)
➁ Check whether the electric leakage breaker conforms to high-harmonic specifications.
(As INV PAC units has inverter, in order to prevent from improper operation, be sure to use the breaker of high-harmonic type.)
RUN light
TIMER light
Green LED
Red LED
Keeps flashing
5-time flash
Yellow LED
4-time flash
5. Troubleshooting
Diagnosis
In case that the compressor
does not start at all and no
sound or vibration exists
Is
power source voltage
OK?
YES
Is the
pressure equalized
at starting OK?
YES
Is the insulation
resistance and resistance
between terminals(1) of
compressor OK?
(1) 0.309Ω or more at 20°C (Model FDC200VSA-W)
YES
To next page
143
-
Content
Compressor startup failure (1/2)
(Model FDC200VSA-W only)
NO
NO
NO
-
'22 • PAC-SM-422
Countermeasure
Check the power source
voltage and correct it.
Check refrigerant amount
and refrigerant circuit.
Replace compressor.