Dimensions and weights
Table 6- 21
Parameter
Dimensions W x H x D [mm]
(max. expansion)
Weight CX32-2 [g]
Ambient conditions
The following conditions apply to modules that are shipped and stored in the original
packaging.
Table 6- 22
Parameter
Permissible ambient temperature
Atmospheric pressure
Permissible relative humidity
Installation altitude
Biological environmental conditions
SIMOTION D4x5-2
Manual, 11/2010
Dimensions and weight of a SIMOTION CX32-2
Without fastening using spacers
With fastening using spacers
without packaging
with packaging
CX32-2 environmental requirements
Transport
Long-term storage
Operation
During transport and storage
During operation (condensation, icing, drip,
spray and splash water not permitted)
Storage
Transport
Operation
Supplementary system components
6.4 CX32-2 controller extension
SIMOTION CX32-2
25 x 380 x 230
25 x 380 x 270
approx. 2600
approx. 3150
Values
-40° C ... +70° C
-25° C ... +55° C
0° C ... +55° C up to 2000 m above sea level.
As of an altitude of 2000 m, the maximum
ambient temperature decreases by 7° C every
1000 m increase in altitude
620 ... 1060 hPa
10 % ... 100 %
5 % ... 90 %
5000 m max. above sea level
Class 1B1 according to EN 60 721-3-1
Class 2B1 according to EN 60 721-3-2
Class 3B1 according to EN 60 721-3-3
1)
103