WALL THERMOSTAT
(OPTIONAL)
A wall thermostat may be installed if desired,
connect the wires as per the wiring diagram.
Use the table below to determine the maximum
wire length.
Note: Preferable if the thermostat is
installed on an interior wall.
Regencyoffers an optional programmable
thermostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or
UL approved may be used.
CAUTION
Do not connect millivolt
wall thermostat wires
to 120V wire.
Thermostat Wire Table
Recommended Maximum Lead
Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size
Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.

DC SPARK IGNITER

BATTERY INSTALLATION

Install the supplied battery into the DC Sparker Box
by opening the battery compartment.
NOTE: The battery in the DC Sparker Box will
need to be replaced annually.
P36-10 Zero Clearance Direct Vent Gas Fireplace |
installation
|