UPS2000-G-(6 kVA-20 kVA)
User Manual
Table 9-12 Backup time parameters for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
efficiency)
Load (%)
100%
80%
50%
30%
Figure 9-4 Backup time curve for the ESS-240V12-9AhBPVBA01/
ESS-240V12-9AhBPVBA04 battery pack (20 kVA, calculated based on 94% battery
efficiency)
Issue 21 (2022-10-13)
Load (W)
Two
Battery
Packs
(min)
18000
4
14400
7
9000
12
5400
26
Copyright © Huawei Technologies Co., Ltd.
9 Technical Specifications
Four
Six Battery
Battery
Packs
Packs
(min)
(min)
12
23
17
29
32
53
57
88
Eight
Battery
Packs
(min)
32
44
70
125
133