Huawei UPS2000-G Series User Manual page 161

Hide thumbs Also See for UPS2000-G Series:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
Issue 21 (2022-10-13)
NO TE
● The bypass frequency range is associated with the ECO frequency range (the bypass
frequency range is ±0.5 Hz, ±1 Hz, ±2 Hz, ±3 Hz, ±4 Hz, ±5 Hz, or ±6 Hz; the ECO
frequency range is ±0.5 Hz, ±1 Hz, ±2 Hz, or ±3 Hz).
The bypass frequency range must be greater than or equal to the current ECO frequency
range (if the ECO frequency range is ±3 Hz, the bypass frequency range is ±3 Hz, ±4 Hz,
±5 Hz, or ±6 Hz). The ECO frequency range must be less than or equal to the current
bypass frequency range (if the bypass frequency range is ±1 Hz, the ECO frequency
range is ±0.5 Hz or ±1 Hz).
● The voltage level is associated with the upper threshold for bypass voltages (10%, 15%,
20%, 25%, or 30%).
If the voltage level is 208 V, the upper threshold for bypass voltages is 10%, 15%
(default), 20%, 25%, or 30%.
If the voltage level is 220 V (line voltage: 380 V), the upper threshold for bypass
voltages is 10%, 15% (default), 20%, or 25%.
If the voltage level is 230 V (line voltage: 400 V), the upper threshold for bypass
voltages is 10%, 15% (default), or 20%.
If the voltage level is 240 V (line voltage: 415 V), the upper threshold for bypass
voltages is 10% or 15% (default).
Copyright © Huawei Technologies Co., Ltd.
D LCD Menus and Parameters
153