Huawei UPS2000-G Series User Manual page 98

Hide thumbs Also See for UPS2000-G Series:
Table of Contents

Advertisement

UPS2000-G-(6 kVA-20 kVA)
User Manual
Issue 21 (2022-10-13)
Table 4-35 Shallow Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description
Timed
Specify whether to enable
shallow
the scheduled shallow
discharge
discharge test. If this
test
parameter is set to Enable,
the system automatically
performs a shallow
discharge test when the test
interval arrives and the
system meets the shallow
discharge conditions. The
parameter is configurable in
any mode.
Time
Set the interval for shallow
interval
discharge tests. The
parameter is configurable in
any mode.
Discharge
Set the proportion of the
ratio
discharge capacity to the
total discharge capacity. The
parameter is configurable in
any mode.
Figure 4-43 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Default Value
Value Range
Disabled
Disabled,
Enabled
60 days
30–90 days
20%
10%–50%
90