User Manual
Step 6 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q1 of the UPS to start loads.
----End
Starting the UPS in Battery Mode
Step 1 Switch on the external battery circuit breaker (if any) or connect battery cables.
Step 2 Press
displayed.
Issue 21 (2022-10-13)
Figure 5-3 Startup operations
On the standby screen, hold down
Startup in the Control menu, and press
displayed. If the UPS starts successfully, it enters normal mode.
NO TE
The two methods in
Step 5
NO TE
To prevent triggering overload protection, start the loads with higher power and then loads
with lower power.
on the control panel. The LCD starts. The initialization screen is
Initial startup
On the Settings wizard screen, set the language (the preset language is
English), system parameters, and battery parameters. After you complete the
settings, press
. The standby screen is displayed.
Figure 5-4 Standby screen displayed after initial startup
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the
standby screen, press
Settings > System Parameters > Output to view output settings: if the
system uses three-phase input three-phase output, set Output mode to
Three-phase; if the system uses three-phase input single-phase output or
single-phase input single-phase output, set Output mode to Single-phase.
Set Voltage level and Frequency level based on the rated voltage and
frequency. Press ESC to return to the standby screen.
Copyright © Huawei Technologies Co., Ltd.
to enter the main menu. Select
are called "startup operations" in this section.
to enter the main menu. Choose Main Menu >
. The Starting message is
5 Operations
100