4.6.3.3 System Parameters Screen

Issue 21 (2022-10-13)
Item
Description
BPS
Set the output dry contact
backfe
associated with bypass backfeed.
ed
When a bypass backfeed alarm is
generated, this dry contact is
enabled.
Faulty
Set the output dry contact
UPS
associated with UPS faults. When
a critical alarm is generated, this
dry contact is enabled.
Parallel screen
Figure 4-28 Parallel screen
Table 4-18 Parallel settings
Item
Description
Single/Parallel
Specifies whether the UPS
works in single mode or
parallel mode. This
parameter is configurable
only after the inverter is
shut down.
Redundant
Set the number of
UPSs
redundant UPSs. This
parameter is configurable
only after the inverter is
shut down.
Output screen
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Default
Value Range
Value
Dry contact
Dry contacts
5
1–6
Dry contact
Dry contacts
6
1–6
Default
Value Range
Value
Single
Single,
Parallel
0
0–3
69