Load/Save configuration

Restoring the previous configuration
Select Restore configuration to restore the previous system configuration.
Caution:
For large cabinet control panels with an internal 10 A power supply (-P
variants), always confirm that the PSU supervision setting is 10 A after restoring
the system configuration (see "PSU supervision" on page 83).
To restore the system configuration:
1. Select Panel setup from the Main menu, and then select Configuration.
2. Select Restore configuration and confirm your selection.
3. Press F4 (Enter), and then press F1 (Back).
4. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Loading and saving configuration files
Select Load configuration or Save configuration to load a system configuration
file from a USB flash drive or to save the current system configuration file to a
USB flash drive.
Note:
Use only FAT32 file system USB flash drives with a maximum capacity of
32 GB.
To load a configuration:
1. Open the control panel door and insert the USB flash drive with the
configuration file into either of the USB type A connectors (see "Cabinet and
PCB layout" on page 19). Close the control panel door.
2. Select Panel setup from the Main menu.
3. Select Configuration, and then select Load configuration.
4. Select the configuration file to load.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
7. Remove the USB flash drive as described in "Removing a USB device" on
page 57.