Front Panel Controls And Indicators - Ziton ZP2-AF2-P Installation Manual

Hide thumbs Also See for ZP2-AF2-P:
Table of Contents

Advertisement

Front panel controls and indicators

Operational features described in this section are not available to all users. More
information on control panel operation and access restrictions can be found in
the topic "User levels" on page 46.
Common controls and indicators
The table below includes information for the common controls and indicators
available for fire, repeater, and evacuation panels.
Table 5: Common controls and indicators
Control/LED
Supply LED
General Test LED
General Disable LED
General Fault LED
Alarm LED
Fire Routing
On/Acknowledged button
and LED
Fire Routing Delay button
and LED
ZP2-A Series Installation Manual
LED colour
Description
Green
Indicates that the system is powered up.
Yellow
Indicates that one or more features or devices are
being tested.
Yellow
Indicates that one or more features or devices are
disabled.
Yellow
Indicates a general fault. The fault LED for the
corresponding device or feature also flashes.
Red
Indicates a fire alarm.
A flashing LED indicates that the alarm was
activated by a detector. A steady LED indicates that
the alarm was activated by a manual call point.
Red
Cancels a previously configured delay as it counts
down and activates fire routing.
A flashing LED indicates that fire routing has been
activated. A steady LED indicates that the fire
routing signal has been acknowledged by the
remote monitoring equipment.
Yellow
Enables or disables a previously configured fire
routing delay. Cancels a delay as it counts down and
activates fire routing.
A steady LED indicates that a delay is configured
and enabled. A flashing LED indicates that a delay is
counting (fire routing is activated when the
configured delay elapses or when the delay is
cancelled).
The countdown for an active (counting) fire routing
delay or extended fire routing delay is also displayed
on the product LCD (see Figure 3 on page 12):
When a fire routing delay is counting (and has
not been extended), the LCD displays FR in T1:
xxx sec.
When an extended fire routing delay is counting
(investigation time), the LCD displays FR in T2:
xxx sec.
Chapter 1: Introduction
7

Advertisement

Table of Contents
loading

Table of Contents