Introduction

User levels

Access to some of the features of this product is restricted by the user level
assigned to a user account.
Caution:
Always change default passwords. When a default password is not
changed, the control panel registers a condition and displays a notification until
the default password is changed. To change a password, see "Changing your
password" on page 66.
Public
The public level is the default user level.
This level allows basic operational tasks, such as responding to a fire alarm or
fault warning at the control panel. No password is required.
Operational tasks for this user level are described in the product operation
manual.
This user level is equivalent to EN 54-2 access level 1.
Operator
The operator level allows additional operational tasks and is reserved for
authorized users who have been trained to operate the control panel. The default
password for the default operator user is 2222. Operational tasks for this user
level are described in the product operation manual.
This user level is equivalent to EN 54-2 access level 2 (reduced).
Maintenance
The maintenance level allows routine maintenance tasks and is reserved for
authorized users who have been trained to operate and maintain the control
panel and fire system. The default password for the default maintenance user
is 3333.
This user level is equivalent to EN 54-2 access level 2.
Installer
The installer level allows full system configuration and is reserved for authorized
users installing and configuring the control panel and fire system. The default
password for the default installer user is 4444.
This user level is equivalent to EN 54-2 access level 3.