Chapter 3: Configuration and commissioning

Zone configuration

Zone configuration options are shown in the table below.
Table 47: Zone configuration options
Option
General config
Zone config
Area config
Test/Disable t_out
Zone overview
The maximum number of zones available is 512 (for all control panels). The zone
number range is 01 to 9999.
Note:
For 2010-2GUI application compatibility, assigned zone numbers must be
in the range 1 to 4095 (zones with higher numbers will be discarded).
Zones in networked control panels are considered global. If two networked
control panels each include, for example, Zone 5, then these are grouped to
create a single Zone 5 configuration within the network.
Remote zones
The control panel also considers an additional zone called remote zone (REMT)
which spans all the zones in the system outside the control panel zones range.
This virtual zone can be configured like any other zone in the system and it is
important to define output group activation requirements when the panel receives
remote alarms.
Assigning loop devices to zones
Create zones by assigning zone numbers to loop devices.
To assign a zone number to a loop device:
1. Select Field setup from the Main menu.
2. Select Loop device configuration.
3. Select the corresponding loop and device.
4. Assign a zone number to the device.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
102
Description
Configures the initial zone, the initial zone for a zone LED indicator (if an
optional zone indicator board is installed), the maximum number of
zones in test, and the number of global zones.
Configures additional zone settings, such as the zone type (normal or
confirmed with corresponding parameters), area, CIT and ACT delays,
disabled or enabled, operation mode, etc.
Configures areas. An area is a group of zones used for alarm
confirmation.
Configures the zone test or disable timeout period. See "Zone test and
disablement timeout" on page 52 for more information.
ZP2-A Series Installation Manual