The Test menu

Use the Test menu to test system features or devices. The following features or
devices can be tested from this menu:
Zones
Control panel input activation
Control panel and loop output activation
Output group activation
Device LED activation
Remote features and devices
Batteries
Note:
Tests for outputs and output groups (local or remote) continue for as long
as the test screen is visible. There is no automatic timeout for the output
activation test and system information will not be visible on the LCD for the
duration of the test. Operation not related to the activation test continues as
normal in the background.
Testing zones
To test a zone:
1. Select Test from the Main menu.
2. Select Zones.
3. Select the zone to test, and then press the jog dial to start the test. Press the
jog dial again to end the test for the selected zone.
By default you can select and test up to a maximum of four zones to test at
the same time (the maximum number of zones in test is configurable - see
"Zone configuration" on page 102).
4. Press F2 (Exit) to exit the menu.
Repeat the above steps to end the zone test.
When an alarm is activated in a zone in test:
The zone test is confirmed on the LCD while the alarm is active
If a zone board is installed and the corresponding zone is included on the
zone board, then the zone alarm LED is flashing or steady (depending on the
source of the alarm)
Fire routing, fire protection, sounders, and programmable activations are not
activated
The control panel resets the initiating device after 5 seconds and clears the
alarm (manual call points must first be closed before an automatic reset can
be applied)
The event is recorded in the event log
ZP2-A Series Installation Manual