Chapter 3: Configuration and commissioning

BMS Configuration

Select BMS Config to configure building management protocol settings (BACnet,
Modbus). By default neither protocol is enabled.
Table 45: BMS configuration options
Option
Protoc
InitPan [1]
Mode [1]
[1] Not applicable for BACnet.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select BMS Config.
3. Configure all required settings.
Initpan is only required when using Modbus in Zonepoint mode.
Zonepoint mode implements Modbus services for 32 networked fire panels
with consecutive addresses (for example, 1 to 32 if the address of the first
panel is defined as 001 in InitPan).
Zone mode implements Modbus services for 128 networked fire panels
(InitPan is not required).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
98
Description
Configures the BMS protocol (NO, BACnet, or
Modbus)
Configures the initial panel address when using
Modbus in Zonepoint mode
Configures the Modbus mode (Zonepoint or Zone)
Default value
NO
001
Zonepoint
ZP2-A Series Installation Manual