Loop Class Configuration; Remote Disable/Enable Configuration - Ziton ZP2-AF2-P Installation Manual

Hide thumbs Also See for ZP2-AF2-P:
Table of Contents

Advertisement

Loop Class configuration

Select Loop Class to configure the installation loop Class (Class A or Class B).
The default setting is Class A.
To configure a loop as Class A or Class B:
1. Select Field setup in Main menu.
2. Select Loop Class and select the loop number (1 for one-loop panel; 1 or 2 for
two-loop panel, etc.).
3. Select Class A or Class B.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Remote disable/enable configuration

Use the Disable/Enable menu to remotely disable and enable system features
and devices in a fire network. Disabled features and devices do not indicate
faults or fire alarms.
If remotely disabling zones in alarm, you must reset the control panel associated
with the zone in alarm to complete the operation.
Remotely disabling or enabling a system feature or device
To remotely disable a feature or device:
1. Select Remote Disable/Enable from the Main menu, and then select Remote
disable.
2. Select Panel, and then select ALL or Firenet ID to define the scope of the
remote disable/enable command (all panels in the network or a single panel
in the network).
3. Select Element, and then select Zone, Device, Group, or Panel.
Enter the zone number, address, or ID for the element that you want to
disable or enable. See Table 67 on page 128 for more information.
If the zone, address, or ID entered doesn't exist, no action is taken.
4. Select Channel.
Enter the channel, if required. See Table 67 on page 128 for more information
5. Select Active, and then select NO (to disable a feature or device) or YES (to
enable a previously disabled feature or device).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F2 (Exit).
ZP2-A Series Installation Manual
Chapter 3: Configuration and commissioning
127

Advertisement

Table of Contents
loading