Figure 7-15 Connecting a USB-to-PS/2 cable and VGA cable
----End

7.2.6.3 Connecting Network Cables

Before connecting or replacing a network cable, use a network cable tester to
ensure that the new network cable is functional.
Procedure
Step 1 Determine the model of the new network cable.
Step 2 Number the new network cable.
Step 3 Lay out the new network cable.
Issue 04 (2020-06-05)
Shielded cables are recommended.
According to the result of the EMC test, if a non-shielded cable is used, the system
cannot respond to the ESD. As a result, the system is suspended and restarts.
The new and old cables must be of the same model or be compatible.
The number of the new network cable must be the same as that of the old
one.
Use the same type of labels for the network cable.
Record the name and number of the local device to be connected on one
side of the label, and those of the peer device on the other side.
Attach the label 2 cm (0.79 in.) away from the end of the network cable.
Lay out the new cable in the same way as the old one. Underfloor cabling is
recommended because it is tidy and easy.
Lay out network cables in the cabinet based on installation requirements. You
are advised to arrange cables in the same way as existing cables. Ensure that
cables are routed neatly and undamaged.
Separate network cables from power cables and signal cables when laying out
the cables.
The minimum bend radius of a network cable is 4 cm (1.57 in.). Ensure that
the cable insulation layer is intact.