Figure 7-23 Securing the cable
Step 4 Connect the other end of the power cable to the AC PDU in the cabinet.
The AC PDU is fastened horizontally in the rear of the cabinet. Connect the power
cable to the socket on the PDU according to the plan.
Step 5 Bundle the power cable to the cable guide using cable ties.
----End

7.2.6.7.2 Connecting DC PSU Cables

Before connecting power cables, ensure that the server has been correctly
installed. For details, see
● Use dedicated power cables to ensure equipment and personal safety.
● Use power cables only for dedicated servers. Do not use them for other devices.
● Connect the power cables of the active and standby PSUs to different power
● Ground the equipment before powering it on.
Procedure
Step 1 Take the spare part out of its ESD bag.
Step 2 Connect the cables to the PSUs.
1.
Issue 04 (2020-06-05)
NO TICE
distribution units (PDUs) to ensure reliable system operation.
Put the OT terminal (for the ground cable) on the screw removed from the
ground hole, install the screw on the ground hole, and tighten the screw. See
(1) in
Figure
7-24.