9. Commissioning & Recommissioning
Installation space is according manual (enough clearances)
Product is installed indoors without any risk of freezing, rain, moisture ingress
Indoor unit is correctly secured to the floor (tank integrated)
Provisions for condensate/ drainage are made (cooling/defrost), without any risk of flooding
All external pipework is insulated
Power supply is installed with a dedicated correctly rated ELCB and cable sizing for the indoor unit
Indoor unit ELCB rating (Amps)
Mains power supply cable size (mm2)
Mains power supply cable length and size to indoor unit (m, mm2)
Voltage between
Voltage between
Voltage between
The power / amperage rating of the primary pump
Default direction of 3way diverting valve

9.4 Air purging

When commissioning and installing the unit, it is very important to remove all air in the water circuit.
Automatic air purging is possible via manually starting the primary pump of the ClimateHub via the self test mode (water
pump On/Off) in the service menu (password 0202) of the wired remote controller.
Before commissioning the unit, make sure to check the following points:
1 The maximum water pressure of the unit is 2.9 bar static pressure.
2 The operating range of leaving water temperature is 15~70˚C at heating conditions and 5~25˚C at cooling conditions.
3 The minimum required water flow for operation is 16 liters/min (this is not the same as the standard or nominal flow, for
details see section 6.1 Flow Rate).
At all times the required water flow rates should remain.
A flow error can stop the compressor.
• Water quality must be according to EN directive 98/83 EC.
• If the unit and the pipes are exposed to freezing temperature, it can cause damage to the hydraulic system. Special
care must be taken to prevent freezing of the total water system.
• The unit is designed to be used in a closed-loop system. Do not use any other components which are designed only for
an open-loop system.
• Never use Zn-coated parts in the water circuit.
• All hydraulic parts including field piping must be insulated to reduce heat loss and condensation.
Installer reference guide / Mono tank integrated type
Indoor unit
L1 - N
V~
L1 - N2*
V~
Yes
Yes
Yes
Yes
Yes
Yes
m
L2 - N*
V~
L3 - N*
L2 - L3*
V~
L3 - L1*
N - PE
W
Room
※ 3-phase models only
No
No
No
No
No
No
A
mm2
mm2
V~
V~
V~
A
DHW
174