8. System configuration
WL for Cooling
• The Water Law setting range and default values:
Main menu
Menu
(FSV)
WL Item
Cooling
20**
• Outdoor air temperature range : Lower limit 1 (#2051, Default 30 ℃, Range : 25 ~ 35 ℃),
Upper limit 2 (#2052, Default 40 ℃, Range : 35 ~ 45 ℃)
– With these default settings, the water outlet temperature by cooling WL can be changed within the outdoor
temperature range of 30 ~ 40 ℃.
• Water out temperature range for UFH/FCU applications respectively :
– Upper limit 1 (#2061/2071, Default 25/18 ℃), Lower limit 2 (#2062/2072, Default 18/5 ℃)
– With these default settings, the water outlet temperature by cooling WL can be changed within the range of
5/18 ~ 18/25 ℃.
• Type of WL for according to cooling devices (UFH/FCU) : #2081 (Default 1 (WL1 for floor),
2 (WL2 for FCU or radiator)
Ts
#2031
#2032
#2021
#2022
#2011
Installer reference guide / Mono tank integrated type
Outdoor Temp. for WL
WL1 (UFH)
Water out
Temp.
WL2 (FCU)
Cooling WL Selection
Heating
WL2 : FCU
WL1 : UFH
#2012
Item
Max (Point ①)
Min (Point ②)
Max (Point ①)
Min (Point ②)
Max (Point ①)
Min (Point ②)
WL Type
Ts
#2061
#2062
#2071
#2072
Ta
Max (Point ① ) / Min (Point ②), Ts : Target Temp., Ta : Ambient Temp.
Step
Unit
FSV
Default Min. Max.
1
2051
1
2052
1
2061
1
2062
1
2071
1
2072
-
-
2081
1(WL1)
Cooling
WL1 : UFH
WL2 : FCU
#2051
#2052
30
25
35
40
35
45
25
5
25
18
5
25
18
5
25
5
5
25
1
2
Ta
133