7. Electrical installation

Additional pump (B7/B8)

• When connecting the additional pump, a relays must be used, in order to prevent electrical damage to the PCB by over
current. This terminal is rated for 0.5A maximum allowable current only.
CAUTION
• The terminal of this product is for the additional pump and the max allowable current is 0.5A
• The maximum allowed quantity of additional pumps is one.
• Maximum allowed power consumption is 100W.
Terminal No.
Function
Additional AC
B7/B8
Water Pump
Installer reference guide / Mono tank integrated type
B1
B3
B5
B7
B9
B11
B13
B2
B4
B6
B8
B10
B12
B14
Neutral
Live
Neutral additional pump
PCB
Terminal block
B7
B8
L
Power
N
Input/output
AC 230V output
B15
B17
B19
B21
B23
B25
B16
B18
B20
B22
B24
B26
Live additional pump
Pump
M/C
Min./Max.
current
Additional pump (for built-in pump
-/100mA
support) 100W max. (B7=N, B8=L)