Muting Module Configuration; Connector Pinouts/Functions - Banner MM-TA-12B Instruction Manual

Muting module
Table of Contents

Advertisement

System Installation

3.3 Muting Module Configuration

The MM-TA-12B Muting Module should be configured before initial checkout and
use. Two banks of DIP switches are located under the access cover for the con-
figuration port. To access the DIP switches, unscrew the two captive, round-head
slot screws on either side of cover and carefully swing the cover open.
Because the MM-TA-12B has redundant microprocessors, two DIP switch banks
(Bank A and Bank B) must be set identically. Failure to set Bank A and Bank B
identically will result in a lockout condition. Power must be OFF when changing
DIP switch settings; changing settings while power is ON will cause a lockout
condition. The parameters to be manually configured are shown in Figure 3-2.
Switch
Switch
Bank B
Bank A
Configuration Port
OFF
ON
Factory
Default
Settings
NOTE: Switch numbers, e.g. "SW 1," refer to
both switch banks A and B.
Figure 3-2. Muting Module manual configuration parameters
3.4 Connector Pin-outs and Functions
All electrical connections are made through either field-wireable or molded quick-
disconnect plugs. (See Specifications in Section 2 and Figure 3-3.)
Total Current Draw Calculation
Total current draw at the machine interface connector is the sum of the draw of
the Muting Module, the mute lamp, the AUX output and mute devices, and the
safeguarding device connected to the MSSI, if the power connections are used.
To calculate the total current draw, add the following:
I
= I
+ I
TOTAL
MM
AUX
I
= 400 mA (MM-TA-12B supply current) I
MM
I
= X < 360 mA (mute lamp current)
ML
I
= X < 2500 mA (MSSI supply current)
MSSI
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Auto/Manual Reset
(See Section 1.3)
Non-Monitored Mute
Lamp Output
(See Section 1.13)
One-Way or
Two-Way Mute
Initiate Sequence
(See Section 1.17)
EDM Disable
(See Section 1.10)
One-Channel or
Two-Channel EDM
(See Section 1.10)
Mute Enable Input
(See Section 1.12)
Backdoor Time-Out
(See Sections 1.14
and 1.15)
* Factory default setting
+ I
+ I
+ I
ML
MD
MSSI
= X < 250 mA (auxiliary device current)
AUX
I
= X < 500 mA (M1-M4 supply current)
MD
MM-TA-12B Muting Module
SW1 ON = Auto Reset
SW1 OFF = Manual Reset*
SW2 ON = Mute Lamp Output not monitored
SW2 OFF = Monitored Mute Lamp Output*
SW3 ON = Two-way muting*
SW3 OFF = One-way muting
SW4 ON = EDM disabled
SW4 OFF = EDM functional*
SW5 ON = Two-Channel EDM*
SW5 OFF = One-Channel EDM
SW6 ON = ME disabled
SW6 OFF = ME functional*
SW7 OFF, SW8 OFF = 30 sec. (Mute on Power-up Disabled)*
SW7 OFF, SW8 ON = 60 sec. (Mute on Power-up Disabled)
SW7 ON, SW8 OFF = OFF (Mute on Power-up Disabled)
SW7 ON, SW8 ON = OFF (Mute on Power-up Enabled)
• Electrical hookup must be made
by Qualified Personnel and must
comply with NEC (National
Electrical Code) and local stan-
dards.
• Make no connections to the
System other than those described
in Section 3 of this manual. Doing
so could result in serious injury
or death.
Instruction Manual
WARNING . . .