Lenovo ThinkSystem DW612S Neptune DWC Instructions Manual page 80

Smm 2 messages and codes reference
Hide thumbs Also See for ThinkSystem DW612S Neptune DWC:

Advertisement

2. If the event persists, ensure the indicated compute node is completely power off, and then reseat it.
(Service technician only)
3. If the event persists, replace the indicated compute node. (Service technician only)
4. If the event persists, please consult with technical service.
• 216F0023: Node 8 BMC: Slot Or Connector, Fault Status asserted was asserted.
The BMC on indicated compute node unable to response to the initial request in 2 minutes after the
compute node inserted.
Severity: Error
Alert Category: Node - Node event
SNMP Trap ID: 560922659
User Action:
1. Reset the BMC on indicated compute node.
2. If the event persists, ensure the indicated compute node is completely power off, and then reseat it.
(Service technician only)
3. If the event persists, replace the indicated compute node. (Service technician only)
4. If the event persists, please consult with technical service.
• 216F0024: Node 9 BMC: Slot Or Connector, Fault Status asserted was asserted.
The BMC on indicated compute node unable to response to the initial request in 2 minutes after the
compute node inserted.
Severity: Error
Alert Category: Node - Node event
SNMP Trap ID: 560922660
User Action:
1. Reset the BMC on indicated compute node.
2. If the event persists, ensure the indicated compute node is completely power off, and then reseat it.
(Service technician only)
3. If the event persists, replace the indicated compute node. (Service technician only)
4. If the event persists, please consult with technical service.
• 216F0025: Node 10 BMC: Slot Or Connector, Fault Status asserted was asserted.
The BMC on indicated compute node unable to response to the initial request in 2 minutes after the
compute node inserted.
Severity: Error
Alert Category: Node - Node event
SNMP Trap ID: 560922661
User Action:
1. Reset the BMC on indicated compute node.
2. If the event persists, ensure the indicated compute node is completely power off, and then reseat it.
(Service technician only)
3. If the event persists, replace the indicated compute node. (Service technician only)
4. If the event persists, please consult with technical service.
• 216F0026: Node 11 BMC: Slot Or Connector, Fault Status asserted was asserted.
The BMC on indicated compute node unable to response to the initial request in 2 minutes after the
compute node inserted.
76
ThinkSystem DW612S Neptune DWC Enclosure SMM 2 Messages and Codes Reference