Smm 2 messages and codes reference
Hide thumbs Also See for ThinkSystem DW612S Neptune DWC:

Advertisement

SNMP Trap ID: 141492652
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01AD: PSU 1 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492653
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01AE: PSU 2 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492654
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01AF: PSU 3 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492655
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01B0: PSU 4 Iout OC: Power Supply, Power Supply Failure detected was asserted.
26
ThinkSystem DW612S Neptune DWC Enclosure SMM 2 Messages and Codes Reference