User Action:
1. Ensure the room temperature remains at the required level.
2. Ensure all fan rotor on power supply operates properly.
3. If the event persists, please consult with technical service.
• 180701ED: PSU Policy Lost: Chassis, transition to Non-Critical from OK was asserted.
The configured power policy has been disabled.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112429
User Action:
Ensure the input and output indicator is lit on and fault indicator is lit off on all power supplies.
• 180701F0: PSoC EPOW Out: Chassis, transition to Non-Critical from OK was asserted.
All compute nodes are notified of power supply input lost condition. The compute nodes might shut down
immediately.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112432
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 180701F1: PSoC Throttle O: Chassis, transition to Non-Critical from OK was asserted.
All compute nodes are notified of power supply overcurrent condition. The compute nodes could enter
power throttling state and affects the performance.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112433
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 180701FB: SMM2 PrimBt Fail: Chassis, transition to Non-Critical from OK was asserted.
The SMM2 unable to boot from the primary flash bank, and instead of booting from secondary flash bank.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 403112443
User Action:
44
ThinkSystem DW612S Neptune DWC Enclosure SMM 2 Messages and Codes Reference