Smm 2 messages and codes reference
Hide thumbs Also See for ThinkSystem DW612S Neptune DWC:

Advertisement

– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C3: PSU 5 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492675
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C4: PSU 6 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492676
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C5: PSU 7 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492677
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01C6: PSU 8 Vout UV: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output voltage reaches the undervoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492678
User Action:
32
ThinkSystem DW612S Neptune DWC Enclosure SMM 2 Messages and Codes Reference