Alert Category: System - SMM2 system event
SNMP Trap ID: 33619980
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
• 0201000D: SMM2 Brd 12V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 12V power rail is lower than lower non-critical threshold.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 33619981
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
• 02010208: SMM2 Brd 1.15V: Voltage sensor, critical event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 1.15V power rail is lower than lower critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33620488
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
• 02010209: SMM2 Brd 1.2V: Voltage sensor, critical event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 1.2V power rail is lower than lower critical threshold.
Severity: Error
Alert Category: System - SMM2 system event
SNMP Trap ID: 33620489
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
.