The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492656
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01B1: PSU 5 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492657
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01B2: PSU 6 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492658
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F01B3: PSU 7 Iout OC: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its output current reaches the overcurrent lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492659
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
.