Information only; no action is required.
• 08080187: PSU 8: Power Supply, Device Inserted / Device Present was asserted.
The indicated power supply is installed in the power supply slot.
Severity: Information
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134742407
User Action:
Information only; no action is required.
• 08080188: PSU 9: Power Supply, Device Inserted / Device Present was asserted.
The indicated power supply is installed in the power supply slot.
Severity: Information
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134742408
User Action:
Information only; no action is required.
• 086F0180: PSU 1: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its input voltage reaches overvoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492608
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 086F0181: PSU 2: Power Supply, Power Supply Failure detected was asserted.
The indicated power supply reports its input voltage reaches overvoltage lockout limit.
Severity: Error
Alert Category: PSU - Power Supply event
SNMP Trap ID: 141492609
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.