Lenovo ThinkSystem DW612S Neptune DWC Instructions Manual page 20

Smm 2 messages and codes reference
Hide thumbs Also See for ThinkSystem DW612S Neptune DWC:

Advertisement

– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 08070793: PSU 2 EPOW: Power Supply, Monitor was asserted.
The indicated power supply reports an early power off warning owing to its input power reaches
undervoltage or overvoltage lockout limit.
Severity: Information
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134678419
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 08070794: PSU 3 EPOW: Power Supply, Monitor was asserted.
The indicated power supply reports an early power off warning owing to its input power reaches
undervoltage or overvoltage lockout limit.
Severity: Information
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134678420
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 08070795: PSU 4 EPOW: Power Supply, Monitor was asserted.
The indicated power supply reports an early power off warning owing to its input power reaches
undervoltage or overvoltage lockout limit.
Severity: Information
Alert Category: PSU - Power Supply event
SNMP Trap ID: 134678421
User Action:
1. Check LED status of indicated power supply as
– If Input Power Good Indicator (IN) is not lit on, check power cord and input voltage of indicated
power supply.
– If Output Power Good Indicator (OUT) is not lit on, reseat indicated power supply.
– If Fault Indicator (!) is lit on, replace indicated power supply.
2. If the event persists, please consult with technical service.
• 08070796: PSU 5 EPOW: Power Supply, Monitor was asserted.
The indicated power supply reports an early power off warning owing to its input power reaches
undervoltage or overvoltage lockout limit.
Severity: Information
16
ThinkSystem DW612S Neptune DWC Enclosure SMM 2 Messages and Codes Reference