Diagnostic messages

Enabling of diagnostic interrupts
You enable the diagnostic interrupts in the device configuration with the basic parameters.
The technology module can trigger the following diagnostic interrupts:
Table 5- 5
Possible diagnostic interrupts
Diagnostic interrupt
Parameter error
Hardware interrupt lost
Channel/component temporarily unavailable
Internal error
Watchdog tripped. Module is defective.
Wire break at digital input A, B or N
Error
Load voltage missing
Short-circuit / overload at external encoder supply
Error at digital outputs
Invalid transition of A/B signals
Not available in "Position input for "Motion Control"" technology object" and "Fast Mode" operating modes
1
TM Count 1x24V (6ES7138‑6AA01‑0BA0) technology module
Manual, 07/2019, A5E33002339-AD
1
Interrupts/diagnostic messages
Monitoring
Monitoring is always active. A diagnostic interrupt is
triggered each time an error is detected.
Monitoring is active if a push-pull switching encoder
has been configured. When an error is detected, a
diagnostic interrupt is only triggered if "Enable diag-
nostic interrupt on wire break" is activated in the de-
vice configuration.
Monitoring is always active. When an error is detected,
a diagnostic interrupt is only triggered if "Enable addi-
tional diagnostic interrupts" is activated in the device
configuration.
5.2 Diagnostic messages