Emerson Rosemount 1208A Reference Manual page 49

Level and flow transmitter
Hide thumbs Also See for Rosemount 1208A:
Table of Contents

Advertisement

Reference Manual
00809-0100-7062
7.2.10
Short circuit
Alarm classification
Event
Device status
Class
Possible cause
Short circuit on the digital output.
Recommended actions
Check cable and connections.
7.2.11
Primary supply voltage over-run
Alarm classification
Event
Device status
Class
Possible cause
Supply voltage is too high.
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
7.2.12
Primary supply voltage under-run
Alarm classification
Event
Device status
Class
Possible cause
Supply voltage is too low.
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
Reference Manual
Short circuit – Check installation
Out of Specification
Error
Primary supply voltage over-run – Check tolerance
Out of specification
Warning
Primary supply voltage under-run – Check tolerance
Out of specification
Warning
Service and troubleshooting
October 2022
49