Mechanical installation
October 2022
•
The transmitter should be mounted with as few internal structures as possible within
the signal beam.
•
Do not mount close to or above the inlet stream.
•
Do not mount the transmitter on a manway cover.
•
Do not position the transmitter directly over a side manway door.
•
Multiple Rosemount 1208A transmitters can be used in the same tank without
interfering with each other.
Figure 3-1: Recommended Mounting Position
L
3.2.2
Free space requirements
If the transmitter is mounted close to a wall or other tank obstruction such as heating coils
and ladders, noise might appear in the measurement signal. See
recommended clearance.
Figure 3-2: Free Space Requirements
Table 3-1: Distance to Tank Wall (L)
Minimum
8 in. (200 mm)
14
L
Table 3-1
Recommended
½ of tank radius
Rosemount 1208A Level and Flow Transmitter
Reference Manual
00809-0100-7062
for