Mechanical installation
October 2022
The transmitter should be mounted with as few internal structures as possible within
the signal beam.
Do not mount close to or above the inlet stream.
Do not mount the transmitter on a manway cover.
Do not position the transmitter directly over a side manway door.
Multiple Rosemount 1208A transmitters can be used in the same tank without
interfering with each other.
Figure 3-1: Recommended Mounting Position
L
3.2.2
Free space requirements
If the transmitter is mounted close to a wall or other tank obstruction such as heating coils
and ladders, noise might appear in the measurement signal. See
recommended clearance.
Figure 3-2: Free Space Requirements
Table 3-1: Distance to Tank Wall (L)
Minimum
8 in. (200 mm)
14
L
Table 3-1
Recommended
½ of tank radius
Rosemount 1208A Level and Flow Transmitter
Reference Manual
00809-0100-7062