15
➢ This function is valid for the present AD module, it is invalid for other AD modules
expanded by couplers.
➢ One AD / DA module can't use multi-measuring ranges, all channels use the same
measuring range, and different modules can match with multi ranges. Please switch
the range depends on actual situation.
➢ Type number 1 and 9 are used for input module and output module, which means
they can't be used for others.
➢ AD module only can use type number 2~8, DA module only can use type number
10~15.
➢ Input voltage (or current) exceeds the measuring range when use AD module, it
will be the maximum value stability.
ZM1116
ZM1117
ZM2111
ZM2112
ZM2113
ZM2114
ZM2115
ZM2116
ZM2117
ZMIO300 Series Hardware Manual Version 1.8
AD module
AD module
Output module
DA module
DA module
DA module
DA module
DA module
DA module
48
0~5V
-5~5V
-
0-10V
-10~10V
4~20mA
0-20mA
0~5V