Interface Definition; Performance And Specification - Zmotion ZMIO300 Series Hardware Manual

Expansion module
Table of Contents

Advertisement

3.2.2.1 Interface Definition

No.
Interface Name
1
Status indication light
2
Local Expansion Front-level
Interface
3
Local Expansion Behind-
level Interface
4
Signal indication light
5
User's terminal

3.2.2.2 Performance and Specification

Item
Power Voltage
Output number
Output type
Output method
Output overcurrent protection
ZMIO300 Series Hardware Manual Version 1.8
Function Description
RUN
Run
indicator
ALM
Error
indicator
Connect with coupler module or expansion submodule,
doesn't support hot plug or discharge.
Connect with expansion submodule, doesn't support
hot plug or discharge.
Related to each channel input signal indication
16 digital outputs/power terminal
Specification
ZMIO300-16DO
24V DC
16
Digital output
Leakage type (NPN, it is low
electric level when outputs)
Maximum is 300mA, and the max trip current is 600mA
27
It will light when runs
normally.
Green
It will light when
communicate wrongly.
ZMIO300-16DOP
Source type (PNP, it is high
electric level when outputs)

Advertisement