Bacnet Telegrams; Bacnet Ms/Tp Telegram Overview; Telegram Types - Grundfos CIU 300 Functional Profile And User Manual

Bacnet ms/tp for hydro mpc, control mpc and multi-e
Table of Contents

Advertisement

10. BACnet telegrams

10.1 BACnet MS/TP telegram overview

All BACnet MS/TP telegrams have the following format:
Preamble
Telegram type
2 bytes:
1 byte
0x55 0xFF
For BACnet MS/TP, the destination address and source address are MAC addresses. See section
A destination address of 255 (0xFF) denotes broadcast.
The Length field specifies the length in bytes of the data field which must be between 0 and 501 bytes long.

10.2 Telegram types

The available telegram types are listed below.
Type
Name
00
Token
01
Poll for master
02
Reply to poll for master
03
Test request
04
Test response
05
BACnet data, expecting reply
06
BACnet data, not expecting reply
07
Reply postponed
22
Destination
Source
1 byte
1 byte
Description
Used to pass network mastership to the destination device.
Discovers the presence of other master devices on the network.
Used by a master to indicate a wish to enter the token ring.
Used to initiate a loopback test.
A reply to a test request telegram.
Used for data transmission where a reply is expected.
Used for data transmission where no reply is expected.
Used by master devices to defer sending a BACnet data reply.
Length
Header CRC
2 bytes,
1 byte
MSB first
3.7 Selecting the BACnet MAC address
Data
Data CRC
Variable,
At most
2 bytes,
[0-501]
LSB first
bytes
(Pad)
1 byte
0xFF
.