Free Spaces; Positioning Of Potentially Flammable Zones Around The Unit; Installing Several Units; Distance To The Wall - Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

4 - DIMENSIONS, CLEARANCES, MINIMUM INSTALLATION DISTANCES

4.3 - Free spaces

The free spaces presented are determined in order to ensure
sufficient working and manoeuvring space to carry out maintenance 
operations on the unit in suitable ergonomic conditions
B C
B
1500
Key:
All dimensions are given in mm.
B
Clearances required for maintenance and air flow
C
Clearance recommended for coil removal
4.4 - Positioning of potentially flammable zones
around the unit
Electrical cabinet side
The complete unit, including all the options and accessories which
are provided by the manufacturer, have been certified for use with 
an A2L refrigerant.
To ensure this, the manufacturer complies with EN 378-2 §6.2.14
and has defined a potentially flammable zone using EN 60079-
10-1 in order to identify where no sources of ignition must be
present.
The manufacturer has then designed the machine so that, if the
unit is used in the manner for which it has been designed, there
are  no  internal  sources  of  ignition  in  the  potentially  flammable 
zone inside the machine.
Therefore, the only residual risk is that a source of ignition is
introduced into the potentially flammable zone by the user.
This is why the manufacturer has decided to show the potentially
flammable  zone  around  the  machine  (see  the  diagram  above) 
into which the user must not introduce any sources of ignition.
This indication is only provided to help our customers to identify
the limits of the flammability risk.
However, the machine itself does not present any risk of explosion
connected to the use of A2L refrigerant.
B
B
1500
60cm
Note (the following information is provided by the manufacturer 
for guidance only. The application of the following directives is the
sole responsibility of the user):
In compliance with the directives 2009/104/EC and 1999/92/EC,
these zones may be qualified as ATEX zones by the user on the 
basis of their own risk analysis, for which they alone remain
responsible. In accordance with the definition given by Annex I of 
the directive 1999/92/EC, this zone may be classified as zone 2 
since it may consist of a location where an explosive atmosphere
consisting  of  a  mixture  of  air  and  flammable  substances  in  the 
form of a gas is not liable to occur during normal operation or, if
it does occur, it only occurs for a short period of time.
If additional equipment is required (motorised valve, pump, etc.), 
it must be:
■ Installed outside of the defined potentially flammable zone 
■ Certified  as  not  being  a  source  of  ignition  for  the  refrigerant 
used.

4.5 - Installing several units

It is recommended to install multiple units in a single row, arranged
as shown in the example below, to avoid recycling air between
the units. If the floor space does not allow this arrangement, contact 
your distributor to assess the various installation options.
1500 mm
1500 mm

4.6 - Distance to the wall

H
Plots
Antivibratiles
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your distributor to assess the various
installation options.
min.
min.
S
h
11