Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions page 81

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

12 - OPTIONS
12.2.6 - Brine option (Option 6B)
Brine production from 5°C to -8 °C is only possible with the
low-temperature brine solution option (6B).
The unit is equipped with insulation on the intake tubes.
The insulation is reinforced on the low-temperature brine solution
option.
Operating range
■ Low water temperature brine solution (ethylene glycol or propylene glycol)
Operating range Standard unit
52
50
48
45
40
35
30
25
Option Brine 6B
20
15
10
5
0
-5
-10
-15
-20
-25
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Leaving water temperature (°C)
1.  Water type heat exchanger ∆T = 5K.
2.
The hydraulic and/or water type heat exchanger module must be must be
protected against frost (option 41 or 42A or 42B) or the loop must be protected
by an antifreeze solution for outdoor temperatures < 0 °C.
3.
These ranges are guidelines only. Verify the operating range with the electronic
catalogue.
Refrigerant charge for the low-temperature brine solution option
30RB/RBP
Refrigerant
(1)
Circuit A
Circuit B
30RB/RBP
Refrigerant
(1)
Circuit A
Circuit B
(1)  For a combination of option 50 and 6B, refer to the unit name plate.
Part load
170R
190R
kg
4,9
7,4
tCO
e
3,3
5,0
2
kg
8,6
8,6
tCO
e
5,8
5,8
2
480R
550R
kg
30,2
20,5
tCO
e
20,4
13,8
2
kg
32,4
20,5
tCO
e
21,9
13,8
2
The operating range is based on:
■ The size of the machine,
■ The type of glycol,
■ Its concentration,
■ The flow rate,
■ The temperature of the glycol solution,
■ The condensing pressure (ambient temperature).
Operating range Unit option 15LS
50
48
45
44
40
35
30
25
Option Brine 6B
20
15
10
5
0
-5
-10
-15
-20
-25
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Key
Operating range at full load
Extension of the operating range, 30RBP unit: Frost protection required
(see note 2).
Operating range of units at part load
Extension of the operating range, unit with option 6B
210R
230R
270R
7,4
8,6
8,6
5,0
5,8
5,8
8,6
8,6
8,6
5,8
5,8
5,8
610R
670R
720R
19,7
20,9
20,9
13,3
14,1
14,1
20,9
20,9
20,9
14,1
14,1
14,1
Part load
Leaving water temperature (°C)
310R
340R
380R
10,8
11,5
15,6
7,3
7,8
10,5
15,1
15,8
15,6
10,2
10,7
10,5
770R
800R
870R
22,5
22,5
26,6
15,2
15,2
18,0
26,6
26,6
26,6
18,0
18,0
18,0
410R
450R
16,2
16,5
10,9
11,1
16,2
19,7
10,9
13,3
950R
26,6
18,0
26,6
18,0
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30rbAquasnap 30rqpAquasnap 30rq

Table of Contents