Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions page 33

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

6 - ELECTRICAL CONNECTION
Table of minimum and maximum cable sections (per phase) for connection to the units
Max. connectable section
30RB-
Tightening
Connection
RBP
torque
hole
Nm
Standard unit
170R
15
M8
190R
15
M8
210R
15
M8
230R
15
M8
270R
15
M8
310R
50
M10
340R
50
M10
380R
50
M10
410R
50
M10
450R
50
M10
480R
50
M10
550R
50
M10
610R
50
M10
670R
50
M10
720R
50
M10
770R
50
M10
800R
50
M10
870R
50
M10
950R
50
M10
Max. connectable section
30RQ-
Tightening
Connection
RQP
torque
hole
Nm
Standard unit
165R
15
M8
180R
15
M8
210R
15
M8
230R
15
M8
270R
15
M8
310R
50
M10
330R
50
M10
370R
50
M10
400R
50
M10
430R
50
M10
470R
50
M10
520R
50
M10
620R
50 / 50
M10 / M10
(a)
660R
(a)
50 / 50
M10 / M10
740R
50 / 50
M10 / M10
(a)
800R
50 / 50
M10 / M10
(a)
860R
50 / 50
M10 / M10
(a)
940R
50 / 50
M10 / M10
(a)
1040R
50 / 50
M10 / M10
(a)
(1)  Connection capacities actually available for each machine. These are defined according to the connection terminal size, the electrical box access opening dimensions, 
and the available space inside the electrical box.
(2)  Selection simulation result considering the hypotheses indicated.
(3)  If the maximum calculated selection is for a 90°C cable type, this means that a selection based on a 70°C cable type can exceed the connection capacity actually 
available. Special attention must be given to selection.
The protection against direct contact at the electrical connection point is compatible with the addition of fanout cables. The installer must determine whether these are
necessary based on the cable sizing calculation.
(a)   30RQ/30RQP units from 620R to 1040R have two power connection points.
Note: The currents considered are given for a machine fitted with a hydraulic module operating at the maximum current.
Calculation of favourable case:
No. 13 Perforated horizontal raceway or
(1)
no. 17 self-supporting cable - PR (90 °C) - 45 °C
Recommended
Section
(2)
max. lug width
qty x mm²
mm
(per phase)
25
1x50
25
1x50
25
1x70
25
1x70
25
2x35
32
2x50
32
2x50
32
2x70
32
2x70
32
2x70
32
2x95
32
2x95
32
2x120
32
2x150
32
2x150
32
2x185
32
2x185
32
2x240
32
2x240
Calculation of favourable case:
No. 13 Perforated horizontal raceway or
(1)
no. 17 self-supporting cable - PR (90 °C) - 45 °C
Recommended
Section
(2)
max. lug width
qty x mm²
mm
(per phase)
25
1x50
25
1x50
25
1x70
25
1x70
25
2x35
32
2x50
32
2x50
32
2x70
32
2x70
32
2x70
32
2x95
32
2x95
32 / 32
2x50 / 2x50
32 / 32
2x50 / 2x50
32 / 32
2x70 / 2x70
32 / 32
2x70 / 2x70
32 / 32
2x70 / 2x70
32 / 32
2x95 / 2x95
32 / 32
2x95 / 2x95
Max. length
for a voltage
Cable type
(3)
drop < 5%
m
-
180
90 °C Cu
180
90 °C Cu
190
90 °C Cu
190
90 °C Cu
170
90 °C Cu
190
90 °C Cu
190
90 °C Cu
200
90 °C Cu
200
90 °C Cu
200
90 °C Cu
210
90 °C Cu
210
90 °C Cu
220
90 °C Cu
220
90 °C Cu
230
90 °C Cu
240
90 °C Cu
240
90 °C Cu
240
90 °C Cu
240
90 °C Cu
Max. length
for a voltage
Cable type
(3)
drop < 5%
m
-
180
90 °C Cu
180
90 °C Cu
190
90 °C Cu
190
90 °C Cu
170
90 °C Cu
190
90 °C Cu
190
90 °C Cu
200
90 °C Cu
200
90 °C Cu
200
90 °C Cu
210
90 °C Cu
210
90 °C Cu
190 / 190
90 °C Cu
190 / 190
90 °C Cu
200 / 200
90 °C Cu
200 / 200
90 °C Cu
200 / 200
90 °C Cu
210 / 210
90 °C Cu
210 / 210
90 °C Cu
Calculation of unfavourable case:
No. 41 Closed conduit - PR (90 °C) - 45 °C
Max. length
Section
for a voltage
(2)
drop < 5%
qty x mm²
(per phase)
2x25
190
2x35
210
2x35
210
2x50
240
2x70
260
2x70
260
2x70
260
2x95
270
2x95
270
2x120
290
2x120
290
2x150
300
2x185
310
2x240
320
2x240
320
4x120
300
4x150
310
4x150
310
4x185
300
Calculation of unfavourable case:
No. 41 Closed conduit - PR (90 °C) - 45 °C
Max. length
Section
(2)
for a voltage
drop < 5%
qty x mm²
(per phase)
2x25
190
2x35
210
2x35
210
2x50
240
2x70
260
2x70
260
2x70
260
2x95
270
2x95
270
2x120
290
2x120
290
2x150
300
2x70 / 2x70
260 / 260
2x70 / 2x70
260 / 260
2x95 / 2x95
270 / 270
2x95 / 2x95
270 / 270
2x120 / 2x120
290 /290
2x120 / 2x120
290 /290
2x150 / 2x150
300 / 300
Cable type
(3)
-
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
Cable type
(3)
-
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
90 °C or 70 °C
33