Nominal System Water Flow Rate Control; Units Without Hydraulic Module; Units With Hydraulic Module And Fixed-Speed Pump - Carrier AQUASNAP 30RBP Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers, reversible heat pumps
Table of Contents

Advertisement

9 - NOMINAL SYSTEM WATER FLOW RATE CONTROL

Refer to the schematic diagram in the "Hydraulic connections"
paragraph for all item references in this chapter.
The water circulation pumps of the units in the range have been
designed to allow the hydraulic modules to operate in all possible
configurations  depending  on  the  specific  system  conditions, 
i.e. with water inlet/outlet temperature differences (Delta T) at full 
load which vary from 3 to 10 K.
This temperature difference required between the water inlet and 
outlet  determines  the  nominal  flow  rate  of  the  system.  Use  the 
specification  provided  when  selecting  the  unit  to  determine  the 
system's operating conditions.
In particular, collect the data to be used for the control of the system
flow rate:
■ For a unit without hydraulic module: nominal pressure drop at
the unit terminals (plate heat exchanger + internal pipe). This 
is measured with pressure gauges that must be installed at the
inlet and outlet of the unit (item 21).
■ U n i t s w i t h f i x e d - s p e e d p u m p s : n o m i n a l f l o w r a t e .
The pressure of the fluid is measured by sensors installed at 
the inlet of the pump and outlet of the unit (items 7 and 10). 
The system calculates the flow rate associated with this
differential pressure. The flow rate can be read directly on the 
user interface (refer to the control manual for the range).
■ Units with variable-speed pumps – control on pressure
differential: pressure differential at the hydraulic module
terminals,
■ Units with variable-speed pumps – control on temperature
differential: nominal temperature difference at the exchanger.
If this information is not available when the system is commissioned,
contact the engineering and design department responsible for
the system to obtain it.
This data can be obtained either from the performance tables
included in the technical documentation (for cases where the water 
type  heat  exchanger  temperature  delta  is  5  K)  or  from  the 
"Electronic Catalogue" selection program for all other applicable 
temperature delta in the range of 3 to 10 K.

9.1 - Units without hydraulic module

General information
The nominal flow rate of the system will be set using a manual 
valve that should be installed on the water outlet pipe (item 22 on 
the typical hydraulic circuit diagram).
Due to the pressure drop it generates on the hydraulic system,
this flow rate control valve is used to set the system pressure/flow 
rate  curve  to  the  pump  pressure/flow  rate  curve,  to  obtain  the 
nominal flow rate at the desired operation point.
This is checked by reading the pressure drop on the unit
(plate heat exchanger + internal piping).
As the exact total system pressure drop is not known upon
commissioning, it is necessary to adjust the water flow rate with 
the control valve to obtain the installation's specific flow rate.
Hydraulic circuit cleaning procedure
■ Open all control valves completely (item 22).
■ Start up the system pump.
■ Read the pressure drop as the difference between the unit inlet 
and outlet pressures on the pressure gauge (item 21).
■ Let the pump run for 2 hours continuously to flush the system's 
hydraulic circuit (presence of contaminating solids).
■ Perform another reading.
■ Compare this value to the initial value.
48
■ A changed value indicates that the filters in the system need 
to  be  removed  and  cleaned.  In  this  case,  close  the  shut-off  
valves on the water inlet and outlet (item 19) and remove the 
filters then clean (items 1 and 20) after draining the hydraulic 
part of the unit (items 6).
■ Remove the air from the circuit (items 5 and 17).
■ Repeat until all fouling is removed from the filter.
Water flow rate adjustment procedure
Once the circuit has been decontaminated, read the pressures on
the  pressure  gauges  (water  inlet  pressure  -  outlet  pressure) 
to determine the pressure drop across the unit terminals (plate 
heat exchanger + internal piping).
Compare the value obtained to the theoretic value of the selection
(WARNING: Take into account the pressure drop on the filter
if it is located between the pressure gauges).
If  the  pressure  drop  reading  is  above  the  specified  value,  this 
indicates that the flow rate at the terminals of the unit (and therefore 
within the system) is too high. In this case, close the control valve 
and read the new difference in pressure.
Proceed by repeatedly closing the control valve (item 22) until the 
nominal flow rate is achieved at the unit's required operation point
NOTE:
If the system has an excessive pressure drop in relation to
the available static pressure delivered by the system's pump,
the nominal water flow rate cannot be obtained (lower
resulting flow rate) and the temperature difference between
the water inlet and outlet of the water type heat exchanger
will be increased.
To reduce the installation's hydraulic system pressure drop, it is
necessary to:
■ Reduce the pressure drops of individual components (bends, 
level changes, options, etc.) as much as possible;
■ Use the correct pipe diameter;
■ Do not extend the hydraulic systems.
9.2 - Units with hydraulic module and fixed-
speed pump
General information
See the paragraph on "Units without hydraulic module"
Hydraulic circuit cleaning procedure
■ Open all control valves completely (item 22).
■ Start up the unit's pump.
■ Read the flow rate on the user interface.
■ Let the pump run for 2 hours continuously to flush the system's 
hydraulic circuit (presence of contaminating solids).
■ Perform another reading.
■ Compare this value to the initial value.
■ A decrease in the flow rate value indicates that the filters in the 
system need to be removed and cleaned. In this case, close
the shut-off valves on the water inlet and outlet (item 19) and 
remove the filters (items 20 and 1) after draining the hydraulic 
part of the unit (items 6).
■ Remove the air from the circuit (items 5 and 17).
■ Repeat until all fouling is removed from the filter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30rbAquasnap 30rqpAquasnap 30rq

Table of Contents