12 - OPTIONS
Total recovery (pressure drop curves for the plate heat exchangers)
100
10
1
1
Heat exchanger water flow rate (l/s)
12.2.4.4 - Operating limits
30RBP 170R-950R units
Total recovery exchanger
Water inlet temperature at start-up
Water outlet temperature during operation
Water inlet temperature on shut-down
Note: Do not exceed the maximum operating temperature.
(1)  On start-up, the water inlet temperature must not be below 25 °C. For installations with a lower temperature, a three-way valve is necessary 
Operating range in cooling mode
50
45
40
46
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-10
-5
0
5
Evaporator water outlet temperature (°C)
Key
Full load
Low temperature brine solution option
Part load for RBP720R-870R
Part load for RBP950R
Notes
1.
Evaporator ∆T = 5K.
2.
The unit must be either equipped with frost protection options for the water
type heat exchangers (evaporator and heat recovery) and the hydraulic
module (if used), or the water loop must be protected against freezing by
the installer with an antifreeze solution
3.
These ranges are guidelines only. Verify the operating range with the
electronic catalogue.
B C D E F
G
10
Part load for
30RBP 720R-870R
30 RBP 950R
10
15
20
25
B
30RBP 170R
C
30RBP 190R-210R
D
30RBP 230R-270R
100
°C
°C
°C
Operating range in heat recovery mode
70
65
63
60
55
54
50
45
40
35
30
25
20
-10
-5
0
Evaporator water outlet temperature (°C)
Key
Full load
Low temperature brine solution option
Limitation to a part load of 50% below an ambient air temperature of -10 °C
Averaged values. Check the electronic catalogue for details of each unit
Limitation to a part load of 50 % below an ambient air temperature of 0 °C
Averaged values. Check the electronic catalogue for details of each unit
Notes
-
Evaporator ∆T = 5K
-
Condenser ∆T = 5K up to 30RBP550 and 8K for sizes 610R to 950R
-
These operating ranges are guidelines only. Verify the operating range
with the electronic catalogue.
E
30RBP 310R-410R
F
30RBP 450R-550R
G
30RBP 610R-950R
Minimum
Maximum
25
60
(1)
30
65
3
70
5
10
15
20
25
79