12 - OPTIONS
12.2.4 - TOTAL HEAT RECOVERY (option 50)
Suitable for heating, domestic hot water production, agriculture and food industry, industrial processes and other hot-water requirements.
With the total heat recovery option it is possible to reduce the energy consumption bill considerably, when compared to conventional
heating equipment such as fossil fuel boilers or electric water tanks.
Operating principle
If hot water production is required, the compressor discharge gases are directed towards the heat recovery condenser. The refrigerant
releases its heat to the hot water that leaves the condenser at a temperature of up to 60 °C. In this way, 100% of the heat rejected by 
the liquid chiller can be used to produce hot water. The hot water temperature is controlled by the chiller's SmartVu
NOTE: Heat recovery is only possible if the unit is producing cooling at the same time.
12.2.4.1 - Physical properties of units with total heat recovery
30RBP
Total recovery exchanger
Water volume circuits A/B
Maximum operating pressure, water side
Hydraulic connections
Connection
External diameter
Operating weight
(1)
Standard unit + total recovery option
Unit with option 15LS + total recovery option
Refrigerant
(3)(4)
Circuit A
Circuit B
30RBP
Total recovery exchanger
Water volume circuits A/B
Maximum operating pressure, water side
Hydraulic connections
Connection
External diameter
Operating weight
(1)
Standard unit + total recovery option
Unit with option 15LS + total recovery option
Refrigerant
(3)(4)
Circuit A
Circuit B
(1)   Weights are guidelines only. Refer to the unit name plate.
(2)  Options: 15LS = Very low sound level, 
(3)  Values are guidelines only. Refer to the unit name plate.
(4)  For a combination of option 50 and 6B, refer to the unit name plate
170R
190R
l
20
kPa
600
600
in
3"
mm
88,9
88,9
kg
1490
1580
kg
1573
1663
(2)
kg
11,5
13,7
tCO
e
7,8
9,2
2
kg
16,2
19,2
tCO
e
10,9
13,0
2
480R
l
44
kPa
600
in
4"
mm
114,3
kg
3110
(2)
kg
3273
kg
30,7
tCO
e
20,7
2
kg
33,4
tCO
e
22,5
2
210R
230R
270R
Brazed-plate heat exchanger
24
24
29
29
600
600
600
Victaulic
3"
3"
3"
3"
88,9
88,9
88,9
1580
1740
1775
1663
1849
1884
R32 / A2L / GWP=675 as per AR4
13,7
19,3
19,7
9,2
13,0
13,3
19,2
19,3
19,7
13,0
13,0
13,3
550R
610R
670R
720R
Brazed-plate heat exchanger
44
61
61
61
600
600
600
600
Victaulic
4"
5"
5"
5"
114,3
139,7
139,7
139,7
3315
3848
4093
4093
3496
3981
4246
4246
R32 / A2L / GWP=675 as per AR4
33,9
41,8
43,2
43,2
22,8
28,2
29,2
29,2
33,9
43,2
43,2
43,2
22,8
29,2
29,2
29,2
control unit
TM
310R
340R
380R
410R
31
31
31
31
600
600
600
600
4"
4"
4"
4"
114,3
114,3
114,3
114,3
2300
2354
4561
2620
2427
2481
4706
2765
20,0
20,8
28,7
29,3
13,5
14,0
19,4
19,8
28,1
28,9
28,7
29,3
19,0
19,5
19,4
19,8
770R
800R
870R
61
61
61
600
600
600
5"
5"
5"
139,7
139,7
139,7
4627
4627
4876
4801
4801
5070
44,7
44,7
50,9
30,2
30,2
34,3
50,9
50,9
50,9
34,3
34,3
34,3
450R
44
600
4"
114,3
3084
3247
30,4
20,5
33,0
22,3
950R
61
600
5"
139,7
4876
5070
50,9
34,3
50,9
34,3
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30rbAquasnap 30rqpAquasnap 30rq

Table of Contents